Alternative strategies
Try our publication planner

Electric Bus Bar

FAM Unit

Uplighters

Technical Specifications - Zone Units

Unit

ZA1

ZA2

ZA3

ZA1S

ZA2S

ZA3S

MCH

3,500

6,500

10,000

3,500

6,500

10,000

COOLING SH  kW

7/12oC 24oC/55%RH

11.3

21.3

33.3

13.7

24.

38.5

WATER HEATING

AIR IN 18oC 80/70oC

6.5

10.5

17.5

7

15

17

ELECTRIC HEATING

kW

8

12

16

8

12

16

VOLTAGE

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

FAN MOTOR kW

0.5

1

1.5

0.5

1

1.5

NOISE

45 dBA

46 dBA

48 dBA

45 dBA

46 dBA

48 dBA

FOOTPRINT

950x800

1,450x800

2,300x800

950x800

1,450x800

2,500x800

 

Unit

ZA30

ZA31

ZA32

ZA33

MCH

9,500

12,000

14,500

16,500

COOLING SH  kW

7/12oC 24oC/55%RH

31.5

39.3

45.1

52.4

WATER HEATING

AIR IN 18oC 80/70oC

14.5

17.5

20.5

24.5

ELECTRIC HEATING

kW

16

20

24

25

VOLTAGE

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

400/415V

3N 50Hz

FAN MOTOR kW

2x1.5

2x2.2

2x2.2

2x3

NOISE

50 dBA

53 dBA

56 dBA

57 dBA

FOOTPRINT

2,100x1,000

2,300x1,000

2,500x1,000

2,500x1,000

 

 

previous page next page